1. You arrive to perform acceptance testing on a newly installed indoor 15 kV switchgear lineup. Covers are removed and conductors are exposed with taped ends. What is thecorrect initial action?
A) Verify the source is de-energized and apply lockout
B) Assume the equipment is safe since it is new
C) Proceed with visual inspection only
D) Begin insulation resistance testing
2. OSHA requires testing of a voltmeterafterverifying absence of voltage when testing circuits above what voltage level?
A) 120 V
B) 240 V
C) 600 V
D) 50 V
3. A 120 VDC circuit draws0.83 amperes. How much power is consumed?
A) 100 W
B) 120 W
C) 145 W
D) 83 W
4. Sample valves should be flushed with at least how much waste liquid before collecting a transformer oil sample?
A) Until temperature stabilizes
B) One gallon
C) One quart
D) One pint
5. Duringprimary current injection testingof a low-voltage circuit breaker, the breaker trips instantaneously at
8× its long-time pickup setting, even though the instantaneous element is set to10×. What is the MOST likely cause?
A) Improper test lead placement
B) CT saturation
C) Incorrect short-time delay setting
D) Thermal memory enabled
질문과 대답:
| 질문 # 1 정답: A | 질문 # 2 정답: C | 질문 # 3 정답: C | 질문 # 4 정답: C | 질문 # 5 정답: B |